Configuration Settings
Start PV Power: 3kW (configurable)
Smart Load Start SOC: 100% (configurable)
Smart Load End SOC: 50% (configurable)
Operational Logic
The Smart Load function activates when both conditions are met simultaneously: available PV power exceeds the set threshold (default 3kW) and battery State of Charge reaches the start SOC level (default 100%). This ensures non-essential loads only operate during periods of genuine energy surplus. Deactivation occurs automatically when either PV power drops below the set threshold or battery SOC falls to the end SOC level (default 50%). This two-factor protection mechanism guarantees system stability while maintaining power availability for essential loads.
During grid-connected operation, the function maintains the same operational parameters, providing consistent smart load management regardless of grid status. The system prioritizes battery charging and essential load supply over smart load operation, ensuring optimal energy allocation at all times.
This intelligent load management solution enables users to maximize solar energy utilization for non-essential applications while maintaining system reliability and protecting battery health through carefully calibrated operational parameters.